Line 46: |
Line 46: |
| | | |
| | | |
− | <center>[[Image:751.12 safety barrier curb dimensions.gif]]</center>
| + | [[Image:751.12.2.1.jpg|center|400px]] |
− | <center>* Use Rustication on Highway Grade Seperations only</center>
| + | All exposed edges shall have either a 1/2-inch radius or a 3/8-inch bevel, unless otherwise noted. |
− | <center>'''Safety Barrier Curb Dimensions'''</center>
| + | |
| + | The values shown above are only applicable for the standard normal crown of two percent. See [[#751.12.2.10 Superelevation Details |EPG 751.12.2.10 Superelevation Details]] for adjustment of values for different cross slopes. |
| + | |
| | | |
| | | |
Line 98: |
Line 100: |
| === 751.12.2.2 Standard Reinforcement Details === | | === 751.12.2.2 Standard Reinforcement Details === |
| | | |
− | {|border="0" cellpadding="10" cellspacing="1" align="center" style="text-align:center"
| + | The single R bar adds to the rigidity of the reinforcement during construction and it is believed to help prevent cracking. The single bar also appears to assist maintaining uniform |
− | | |
− | |[[Image:751.12 r-bar no wearing surface.gif]]
| |
− | |[[Image:751.12 r1-bar no wearing surface.gif]]
| |
− | |[[Image:751.12 r2-bar no wearing surface.gif]]
| |
− | |-
| |
− | !rowspan="2" valign="top"|R-Bar<br/>Required for Slip Form Option
| |
− | !R1-Bar<br/>Shape 19
| |
− | !R2-Bar<br/>Shape 15
| |
− | |-
| |
− | !colspan="2"|R1 & R2-Bars permissible<br/>only when Slip Forming<br/>not allowed (*)
| |
− | |-
| |
− | |colspan="3"|[[Image:751.12 16in standard safety barrier curb no wearing surface.gif]]
| |
− | |-
| |
− | !colspan="3"|16" Safety Barrier Curb
| |
− | |}
| |
− | <blockquote>
| |
− | (*) The single R bar adds to the rigidity of the reinforcement during construction and it is believed to help prevent cracking. The single bar also appears to assist maintaining uniform
| |
| reinforcement cover. | | reinforcement cover. |
− | </blockquote>
| |
| | | |
| + | Use same grade reinforcing steel in barrier curb as in slab. |
| | | |
| + | Splice length for #5 bars in barrier curb shall be 37 inches. |
| | | |
− | {|border="0" cellpadding="2" cellspacing="1" align="center" style="text-align:center"
| + | All bars are epoxy coated. All bent bars are formed using stirrup bends except for the R1, K4 and K11 bars. |
− | !colspan="4"|Reinforcement (No Wearing Surface)
| |
− | |-
| |
− | |rowspan="3"|[[Image:751.12 r-bar no wearing surface.gif]]
| |
− | |rowspan="3"|[[Image:751.12 16in safety barrier curb no wearing surface.gif]]
| |
− | |[[Image:751.12 r3-bar no wearing surface.gif]]
| |
− | |[[Image:751.12 r4-bar no wearing surface.gif]]
| |
− | |-
| |
− | !#5-R3<br/>Shape 19
| |
− | !#5-R4<br/>Shape 27 (*)
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 r-bar permissible shape no wearing surface.gif]]
| |
− | |-
| |
− | !valign="top"|R-Bar
| |
− | !valign="top"|16" Safety Barrier Curb
| |
− | !colspan="2"|R-Bar Permissible<br/>Alternate Shape (**)
| |
− | |-
| |
− | |colspan="4"|
| |
− | |-
| |
− | !colspan="4"|Reinforcement (1 3/4" Wearing Surface)
| |
− | |-
| |
− | |rowspan="3"|[[Image:751.12 r-bar 1.75 in wearing surface.gif]]
| |
− | |rowspan="3"|[[Image:751.12 16in safety barrier curb 1.75 in wearing surface.gif]]
| |
− | |[[Image:751.12 r3-bar 1.75 in wearing surface.gif]]
| |
− | |[[Image:751.12 r4-bar 1.75 in wearing surface.gif]]
| |
− | |-
| |
− | !#5-R3<br/>Shape 19
| |
− | !#5-R4<br/>Shape 27
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 r-bar permissible shape 1.75 in wearing surface.gif]]
| |
− | |-
| |
− | !valign="top"|R-Bar
| |
− | !valign="top"|16" Safety Barrier Curb
| |
− | !colspan="2"|R-Bar Permissible<br/>Alternate Shape (**)
| |
− | |-
| |
− | |colspan="4"|
| |
− | |-
| |
− | !colspan="4"|Reinforcement (2 1/4" Wearing Surface)
| |
− | |-
| |
− | |rowspan="3"|[[Image:751.12 r-bar 2.25 in wearing surface.gif]]
| |
− | |rowspan="3"|[[Image:751.12 16in safety barrier curb 2.25 in wearing surface.gif]]
| |
− | |[[Image:751.12 r3-bar 2.25 in wearing surface.gif]]
| |
− | |[[Image:751.12 r4-bar 2.25 in wearing surface.gif]]
| |
− | |-
| |
− | !#5-R3<br/>Shape 19
| |
− | !#5-R4<br/>Shape 27
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 r-bar permissible shape 2.25 in wearing surface.gif]]
| |
− | |-
| |
− | !valign="top"|R-Bar
| |
− | !valign="top"|16" Safety Barrier Curb
| |
− | !colspan="2"|R-Bar Permissible<br/>Alternate Shape (**)
| |
− | |-
| |
− | |colspan="4" align="left"|(*) Increase leg for latex or low slump concrete wearing surface.
| |
− | |-
| |
− | |colspan="4" align="left"|(**) The R3 bar and #5 bottom transverse slab bar in cantilever (P/S panels only) combination may be<br/>furnished as one bar as shown, at the contractor's option.
| |
− | |}
| |
− | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
| |
− | |Note:
| |
− | |align="left"|Use same grade reinforcing steel in Barrier Curb as in slab. Splice length for #5 bars in Barrier Curb = 35".
| |
− | |-
| |
− | |
| |
− | |align="left"|Dimensions shown are also typical for structures with latex or low slump concrete (except as indicated).
| |
− | |}
| |
| | | |
− | === 751.12.2.3 End Bent Reinforcement ===
| + | '''(No Wearing Surface)''' |
| | | |
− | {|border="0" cellpadding="1" cellspacing="0" align="center" style="text-align:center"
| + | Dimensions shown are also typical for structures with latex or low slump concrete (except as indicated). |
− | |+'''Non-Integral End Bents'''
| + | [[image:751.12.2.2 no wearing.jpg|center|750px]] |
− | |colspan="2"|[[Image:751.12 non-integral end bent end elevation of barrier curb.gif]]
| |
− | |colspan="2"|[[Image:751.12 non-integral end bent elevation of barrier curb.gif]]
| |
− | |-
| |
− | !colspan="2"|End Elevation
| |
− | !colspan="2"|Elevation of Barrier Curb
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 non-integral end bent section a-a.gif]]
| |
− | |[[Image:751.12 non-integral end bent section b-b.gif]] | |
− | |[[Image:751.12 non-integral end bent section c-c.gif]] | |
− | |-
| |
− | !colspan="2"|Section A-A
| |
− | !Section B-B
| |
− | !Section C-C
| |
− | |-
| |
− | |align="right"|*
| |
− | |colspan="3" align="left"|Spaced with #5-K4 bars.
| |
− | |-
| |
− | |align="right"|**
| |
− | |colspan="3" align="left"|Fit bar to follow transition face of curb.
| |
− | |}
| |
| | | |
| | | |
− | {|border="0" cellpadding="1" cellspacing="0" align="center" style="text-align:center"
| + | '''(1¾” Wearing Surface)''' |
− | |colspan="5"|All bars are epoxy coated.
| + | [[image:751.12.2.2 1 3-4 wearing.jpg|center|750px]] |
− | |-
| |
− | |colspan="5"|All bars are stirrup bends except for K4, K9, K10 & K11.
| |
− | |-
| |
− | |[[Image:751.12 non-integral end bent k1.gif]]
| |
− | |[[Image:751.12 non-integral end bent k2.gif]]
| |
− | |[[Image:751.12 non-integral end bent k3.gif]]
| |
− | |[[Image:751.12 non-integral end bent k4.gif]]
| |
− | |[[Image:751.12 non-integral end bent k5.gif]]
| |
− | |-
| |
− | !#5-K1<br/>Shape 19
| |
− | !#5-K2<br/>Shape 14
| |
− | !#5-K3<br/>Shape 27
| |
− | !#5-K4<br/>Shape 7
| |
− | !#5-K5<br/>Shape 25
| |
− | |-
| |
− | |[[Image:751.12 non-integral end bent k6.gif]]
| |
− | |[[Image:751.12 non-integral end bent k7.gif]]
| |
− | |[[Image:751.12 non-integral end bent k8.gif]]
| |
− | |colspan="2"|[[Image:751.12 non-integral end bent k9.gif]]
| |
− | |-
| |
− | !#5-K6<br/>Shape 25
| |
− | !#5-K7<br/>Shape 25
| |
− | !#5-K8<br/>Shape 25
| |
− | !colspan="2"|#5-K9<br/>Shape 20
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 non-integral end bent k10.gif]]
| |
− | |colspan="2"|[[Image:751.12 non-integral end bent k11.gif]] | |
− | |rowspan="2" align="left"|(*) Increase leg for slab<br/>thickness greater than<br/>8 1/2".
| |
− | |-
| |
− | !colspan="2"|#4-K10<br/>Shape 20
| |
− | !colspan="2"|#5-K11<br/>Shape 8
| |
− | |}
| |
| | | |
| + | |
| + | '''(2¼” Wearing Surface)''' |
| + | [[image:751.12.2.2 2 1-4 wearing.jpg|center|750px]] |
| | | |
| + | === 751.12.2.3 End Bent Reinforcement === |
| | | |
− | <div id="integral end bent barrier curb"></div>
| + | See [http://www.modot.org/business/standard_drawings2/Barrier_curbs_new_title_block.htm barrier curb standard drawings] for the placement of the following reinforcement. |
− | {|border="0" cellpadding="1" cellspacing="0" align="center" style="text-align:center"
| |
− | |+'''Integral End Bents'''
| |
− | |colspan="2"|[[Image:751.12 integral end bent end elevation of barrier curb.gif]]
| |
− | |colspan="2"|[[Image:751.12 integral end bent elevation of barrier curb.gif]]
| |
− | |-
| |
− | !colspan="2"|End Elevation
| |
− | !colspan="2"|Elevation of Barrier Curb
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 integral end bent section a-a.gif]]
| |
− | |[[Image:751.12 integral end bent section b-b.gif]]
| |
− | |[[Image:751.12 integral end bent section c-c.gif]]
| |
− | |-
| |
− | !colspan="2"|Section A-A
| |
− | !Section B-B
| |
− | !Section C-C
| |
− | |-
| |
− | |align="right"|*
| |
− | |colspan="3" align="left"|Spaced with #5-K4 bars.
| |
− | |-
| |
− | |align="right"|**
| |
− | |colspan="3" align="left"|Fit bar to follow transition face of curb.
| |
− | |-
| |
− | |align="right" valign="top"|***
| |
− | |colspan="3" align="left"|On skewed structures, if end K3 bar does not meet the Min. 1 1/2" clearance<br/>from front face of diaphragm, a K12 bar may be substituted.
| |
− | |}
| |
| | | |
| + | All bars are epoxy coated. All bent bars are formed using stirrup bends except for the K4 and K11 bars. |
| | | |
− | {|border="0" cellpadding="1" cellspacing="2" align="center" style="text-align:center"
| + | '''Integral End Bents and Semi-Deep Abutments''' |
− | |colspan="5"|All bars are epoxy coated.
| + | [[image:751.12.2.3 Integral 1.jpg|center|750px]] |
− | |-
| + | [[image:751.12.2.3 Integral 2.jpg|center|750px]] |
− | |colspan="5"|All bars are stirrup bends except for K4, K9, K10 & K11.
| |
− | |-
| |
− | |[[Image:751.12 integral end bent k1.gif]]
| |
− | |[[Image:751.12 integral end bent k2.gif]]
| |
− | |[[Image:751.12 integral end bent k3.gif]] | |
− | |[[Image:751.12 integral end bent k4.gif]] | |
− | |[[Image:751.12 integral end bent k5.gif]]
| |
− | |-
| |
− | !#5-K1<br/>Shape 19
| |
− | !#5-K2<br/>Shape 14
| |
− | !#5-K3<br/>Shape 27
| |
− | !#5-K4<br/>Shape 7
| |
− | !#5-K5<br/>Shape 25
| |
− | |-
| |
− | |[[Image:751.12 integral end bent k6.gif]]
| |
− | |[[Image:751.12 integral end bent k7.gif]]
| |
− | |[[Image:751.12 integral end bent k8.gif]]
| |
− | |colspan="2"|[[Image:751.12 integral end bent k9.gif]]
| |
− | |-
| |
− | !#5-K6<br/>Shape 25
| |
− | !#5-K7<br/>Shape 25
| |
− | !#5-K8<br/>Shape 25
| |
− | !colspan="2"|#5-K9<br/>Shape 20
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 integral end bent k10.gif]]
| |
− | |colspan="2"|[[Image:751.12 integral end bent k11.gif]] | |
− | |[[Image:751.12 integral end bent k12.gif]] | |
− | |-
| |
− | !colspan="2"|#4-K10<br/>Shape 20
| |
− | !colspan="2"|#5-K11<br/>Shape 8
| |
− | !#5-K12<br/>Shape 27
| |
− | |}
| |
| | | |
| | | |
| + | '''*''' On skewed integral end bents, if the end K3 bars do not meet the minimum 1 1/2" clearance from the front face of the diaphragm, a K12 bar shall be substituted. |
| | | |
| + | '''Non-Integral End Bents''' |
| + | [[image:751.12.2.3 Non-integral 1.jpg|center|750px]] |
| + | [[image:751.12.2.3 Non-integral 2.jpg|center|750px]] |
| | | |
− | <div id="barrier curb details-semi deep"></div>
| |
− | {|border="0" cellpadding="1" cellspacing="0" align="center" style="text-align:center"
| |
− | |+'''Semi-Deep Abutments'''
| |
− | |colspan="4"|[[Image:751.12 semi-deep abutment elevation of barrier curb.gif]]
| |
− | |-
| |
− | !colspan="4"|Elevation of Barrier Curb
| |
− | |-
| |
− | |width="35%"|[[Image:751.12 semi-deep abutment end elevation of barrier curb.gif]]
| |
− | |width="35%"|[[Image:751.12 semi-deep abutment section a-a.gif]]
| |
− | |colspan="2"|[[Image:751.12 semi-deep abutment section b-b.gif]]
| |
− | |-
| |
− | !End Elevation
| |
− | !Section A-A
| |
− | !colspan="2"|Section B-B
| |
− | |-
| |
| | | |
− | |rowspan="2"|[[Image:751.12 semi-deep abutment section c-c.gif]]
| + | === 751.12.2.4 Slip-Form Reinforcement Details === |
− | |rowspan="2"|[[Image:751.12 semi-deep abutment section d-d.gif]]
| |
− | |align="right" width="5%"|*
| |
− | |colspan="4" align="left" |Spaced with #5-K4 bars.
| |
− | |-
| |
− | |align="right" |**
| |
− | |colspan="4" align="left" |Fit bar to follow transition face of curb.
| |
− | |-
| |
− | !Section C-C
| |
− | !Section D-D
| |
− | |
| |
− | |
| |
− | |}
| |
| | | |
| + | Optional slip-form safety barrier curb details shall be placed on all jobs (except prestressed double-tee structures) where applicable. |
| | | |
− | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
| + | Add #5 cross bracing C bars for slip-form option. |
− | |colspan="5"|All bars are epoxy coated.
| |
− | |-
| |
− | |colspan="5"|All bars are stirrup bends except for K4, K9, K10 & K11.
| |
− | |-
| |
− | |[[Image:751.12 semi-deep abutment k1.gif]]
| |
− | |[[Image:751.12 semi-deep abutment k2.gif]]
| |
− | |[[Image:751.12 semi-deep abutment k3.gif]]
| |
− | |[[Image:751.12 semi-deep abutment k4.gif]]
| |
− | |[[Image:751.12 semi-deep abutment k5.gif]]
| |
− | |-
| |
− | !#5-K1<br/>Shape 19
| |
− | !#5-K2<br/>Shape 14
| |
− | !#5-K3<br/>Shape 27
| |
− | !#5-K4<br/>Shape 7
| |
− | !#5-K5<br/>Shape 25
| |
− | |-
| |
− | |[[Image:751.12 semi-deep abutment k6.gif]]
| |
− | |[[Image:751.12 semi-deep abutment k7.gif]]
| |
− | |[[Image:751.12 semi-deep abutment k8.gif]]
| |
− | |colspan="2"|[[Image:751.12 semi-deep abutment k9.gif]]
| |
− | |-
| |
− | !#5-K6<br/>Shape 25
| |
− | !#5-K7<br/>Shape 25
| |
− | !#5-K8<br/>Shape 25
| |
− | !colspan="2"|#5-K9<br/>Shape 20
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 semi-deep abutment k10.gif]]
| |
− | |colspan="2"|[[Image:751.12 semi-deep abutment k11.gif]]
| |
− | |[[Image:751.12 semi-deep abutment k12.gif]]
| |
− | |-
| |
− | !colspan="2"|#4-K10<br/>Shape 20
| |
− | !colspan="2"|#5-K11<br/>Shape 8
| |
− | !#5-K12<br/>Shape 27
| |
− | |}
| |
| | | |
| + | In each span, the length of the C bars is based on the shortest distance between the joints for that span. |
| | | |
| + | The length of the C bars above the wings (above the approach slab for median barriers) shall provide 1 1/2ʺ clearance to the joint at the end bent and 1 1/2ʺ clearance to the start of the transition for the guard rail attachment (to the end of the barrier for median barriers). A series of cross bracing C bars shall be used to limit the length of the C bars to 12 feet. |
| | | |
− | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
| + | List C bars in the Bill of Reinforcing Steel and note that bars are for the slip-form option only. |
− | |+'''Continuous Concrete Slab'''
| |
− | |colspan="2"|[[Image:751.12 cont conc slab end bent end elevation of barrier curb.gif]]
| |
− | |colspan="2"|[[Image:751.12 cont conc slab end bent elevation of barrier curb.gif]]
| |
− | |-
| |
− | !colspan="2"|End Elevation
| |
− | !colspan="2"|Elevation of Barrier Curb
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 cont conc slab end bent section a-a.gif]]
| |
− | |[[Image:751.12 cont conc slab end bent section b-b.gif]]
| |
− | |[[Image:751.12 cont conc slab end bent section c-c.gif]]
| |
− | |-
| |
− | !colspan="2"|Section A-A
| |
− | !Section B-B
| |
− | !Section C-C
| |
− | |-
| |
− | |align="right"|*
| |
− | |colspan="3" align="left"|Spaced with #5-K4 bars.
| |
− | |-
| |
− | |align="right"|**
| |
− | |colspan="3" align="left"|Fit bar to follow transition face of curb.
| |
− | |}
| |
| | | |
| + | See [http://www.modot.org/business/standard_drawings2/Barrier_curbs_new_title_block.htm barrier curb standard drawings] for the required details. |
| | | |
− | {|border="0" cellpadding="1" cellspacing="2" align="center" style="text-align:center"
| + | === 751.12.2.5 SBC for Wing with Detached Wing Wall === |
− | |colspan="5"|All bars are epoxy coated.
| |
− | |-
| |
− | |colspan="5"|All bars are stirrup bends except for K4, K9, K10 & K11.
| |
− | |-
| |
− | |[[Image:751.12 cont conc slab end bent k1.gif]]
| |
− | |[[Image:751.12 cont conc slab end bent k2.gif]]
| |
− | |[[Image:751.12 cont conc slab end bent k3.gif]]
| |
− | |[[Image:751.12 cont conc slab end bent k4.gif]]
| |
− | |[[Image:751.12 cont conc slab end bent k5.gif]]
| |
− | |-
| |
− | !#5-K1<br/>Shape 19
| |
− | !#5-K2<br/>Shape 14
| |
− | !#5-K3<br/>Shape 27
| |
− | !#5-K4<br/>Shape 7
| |
− | !#5-K5<br/>Shape 27
| |
− | |-
| |
− | |[[Image:751.12 cont conc slab end bent k6.gif]]
| |
− | |[[Image:751.12 cont conc slab end bent k7.gif]]
| |
− | |[[Image:751.12 cont conc slab end bent k8.gif]]
| |
− | |colspan="2"|[[Image:751.12 cont conc slab end bent k9.gif]]
| |
− | |-
| |
− | !#5-K6<br/>Shape 27
| |
− | !#5-K7<br/>Shape 27
| |
− | !#5-K8<br/>Shape 27
| |
− | !colspan="2"|#5-K9<br/>Shape 20
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 cont conc slab end bent k10.gif]]
| |
− | |colspan="2"|[[Image:751.12 cont conc slab end bent k11.gif]]
| |
− | |
| |
− | |-
| |
− | !colspan="2"|#4-K10<br/>Shape 20
| |
− | !colspan="2"|#5-K11<br/>Shape 8
| |
− | |
| |
− | |-
| |
− | |align="right" valign="top"|*
| |
− | |colspan="4" align="left" valign="top"|According to the development length allowed with the slab depth used, bar may or may not be hooked. Development length starts at slab/barrier interface, basic development length for a straight, #5 epoxy coated bar is 18".
| |
− | |-
| |
− | |align="right" valign="top"|**
| |
− | |colspan="4" align="left" valign="top"|Length varies depending on slab depth. Extend bar to within 1" of construction joint at bottom of slab.
| |
− | |-
| |
− | |align="right" valign="top"|***
| |
− | |colspan="4" align="left" valign="top"|Use Shape 11 or create shape as necessary when development length requires hook.
| |
− | |}
| |
− | | |
− | === 751.12.2.4 Slip-Form Reinforcement Details ===
| |
− | | |
− | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
| |
− | | |
− | |[[Image:751.12 section at end bent (optional slip-form barrier).gif]]
| |
− | |-
| |
− | !Section at End Bent (Optional Slip-Form Barrier)
| |
− | |-
| |
− | |
| |
− | |-
| |
− | |[[Image:751.12 section near joint (optional slip-form barrier).gif]]
| |
− | |-
| |
− | !Section Near Joints (Optional Slip-Form Barrier)
| |
− | |-
| |
− | |
| |
− | |-
| |
− | |[[Image:751.12 optional slip-form barrier section a-a.gif]]
| |
− | |-
| |
− | !Section A-A
| |
− | |-
| |
− | |(*) Each side of Joint Location.
| |
− | |}
| |
| | | |
− | '''NOTE TO DETAILER:'''
| + | If the detached wing wall has more than one section, see the Structural Project Manager for possible additional joints in the safety barrier curb (between sections). |
| | | |
− | Optional Slip-Form Safety Barrier Curb details shall be placed on all jobs (except Prestressed Double-Tee Structures) where applicable.
| + | The following details are for illustration purpose only: |
− |
| |
− | Add #5 cross bracing bars for Slip-Form option. Base the length of these bars on the shortest distance between joints throughout the structure. Show the C-Bars in the Bar List and note that these bars are for the Slip-Form option only.
| |
| | | |
− | === 751.12.2.5 SBC for Wing with Detached Wing Wall ===
| + | [[image:751.12.2.5 Non-integral.jpg|center|650px]] |
| | | |
− | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
| + | [[image:751.12.2.5 Integral.jpg|center|650px]] |
| | | |
− | |colspan="2"|[[Image:751.12 safety barrier curb on non-integral end bent.gif]]
| |
− | |-
| |
− | !colspan="2"|SBC on Non-Integral End Bent (*)
| |
− | |-
| |
− | |
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 safety barrier curb on integral end bent.gif]]
| |
− | |-
| |
− | !colspan="2"|SBC on Integral End Bent (*)
| |
− | |-
| |
− | |align="right"|(*)
| |
− | |align="left"|Detached Wing Wall shown is for illustration purpose only.
| |
− | |-
| |
− | |
| |
− | |align="left"|If the detached wing wall has more than one section, see the Structural Project Manager<br/>for possible additional joints in the safety barrier curb (between sections).
| |
− | |}
| |
| | | |
| === 751.12.2.6 Guardrail Attachment Detail === | | === 751.12.2.6 Guardrail Attachment Detail === |
| | | |
| + | See [http://www.modot.org/business/standard_drawings2/Barrier_curbs_new_title_block.htm barrier curb standard drawings] for the required details. |
| | | |
− | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
| + | [[image:751.12.2.6.jpg|center|450px]] |
| | | |
− | |[[Image:751.12 guard rail attachment detail part elevation a-a.gif]]
| |
− | |[[Image:751.12 guard rail attachment detail part elevation.gif]]
| |
− | |-
| |
− | !Part Elevation A-A
| |
− | !Part Elevation
| |
− | |-
| |
− | |
| |
− | |[[Image:751.12 guard rail attachment detail part plan.gif]]
| |
− | |-
| |
− | |
| |
− | !Part Plan
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 guard rail attachment detail auxiliary view.gif]]
| |
− | |-
| |
− | !colspan="2"|Auxiliary View
| |
− | |}
| |
| | | |
− | === 751.12.2.7 Joint & Rustication Details === | + | === 751.12.2.7 Joint Details === |
| | | |
| '''Curb Expansion Joints.''' Openings required for expansion shall be provided in the barrier curb in conjunction with deck joints. For details of expansion joints in barrier curb see expansion device details. | | '''Curb Expansion Joints.''' Openings required for expansion shall be provided in the barrier curb in conjunction with deck joints. For details of expansion joints in barrier curb see expansion device details. |
| | | |
− | '''Curb Joints.''' 1/4 in. joints are located in the barrier curb at locations of negative moments to prevent cracking in the barrier curb. These joints are required when decks are continuous over intermediate bents for both continuous and simple span structures. These joints are also required at the front face of integral end bents. For details of 1/4 in. curb joints at integral end bents see integral end bent details. | + | '''Curb Joints.''' 1/4 in. joints are located in the barrier curb at locations of negative moments to prevent cracking in the barrier curb. These joints are required when decks are continuous over intermediate bents for both continuous and simple span structures. These joints are also required at the front face of integral end bents. For placement of curb joints at integral end bents see integral end bent details. The following details provide guidance on locating curb joints near intermediate bents. |
| | | |
− | '''Rustication.''' Rustication shall be used on grade separations only. Rustication shall be terminated four feet from the end of the barrier curb.
| + | [[image:751.12.2.7.jpg|center|800px]] |
| | | |
− | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
| + | The details for curb joints are included on the [http://www.modot.org/business/standard_drawings2/Barrier_curbs_new_title_block.htm barrier curb standard drawings]. |
− | | |
− | !colspan="3"|Cast-In-Place Barrier Curbs
| |
− | |-
| |
− | |colspan="3"|[[Image:751.12 joint and rustication details plan of curb joints.gif]]
| |
− | |-
| |
− | | || || width=400px | Note: Sawcut between spans shall be offset from centerline of intermediate bent to match any existing offset.
| |
− | |-
| |
− | !align="right"|Continuous Structures Part Plan
| |
− | ||
| |
− | ! Continuous Re-Deck of Simple Span Structures Part Plan
| |
− | |-
| |
− | |colspan="3"|
| |
− | |-
| |
− | |colspan="3"|[[Image:751.12 joint and rustication details all types of cont structure elevation.gif]]
| |
− | |-
| |
− | !colspan="3"| Part Section Showing Placement of Joints
| |
− | |}
| |
− | {|cellspacing="1" align="center"
| |
− | |align="right" valign="top"|*||One space = 1/4 Span to nearest 1 in. increment (Span < 40 ft.)
| |
− | |-
| |
− | | || One space = 10 ft. (Span = 40 ft. to 125 ft.)
| |
− | |-
| |
− | | || Two spaces = 10 ft. (Span > 125 ft.)
| |
− | |}
| |
− | | |
− | | |
− | | |
− | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
| |
− | | |
− | !colspan="2"|Optional Slip-Form Barrier Curbs
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 joint and rustication details optional slip-form section thru joint and section a-a.gif]]
| |
− | |-
| |
− | !width="410pt"|Section A-A
| |
− | !width="300pt"|Section Thru Joint
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 joint and rustication details optional slip-form all types of cont structure elevation.gif]]
| |
− | |-
| |
− | !colspan="2"|Part Section Showing Placement of Joints
| |
− | |}
| |
− | | |
− | {|cellspacing="1" align="center"
| |
− | |}
| |
− | | |
− | | |
− | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
| |
− | |-
| |
− | |colspan="2"|[[Image:751.12 joint and rustication details optional slip-form part plan continuous structures.gif]]
| |
− | |-
| |
− | | || width="300px"|Note: Sawcut between spans shall be offset from centerline of intermediate bent to match any existing offset.
| |
− | |-
| |
− | !Continuous Structures Part Plan
| |
− | !Continuous Re-Deck of Simple Span Structures Part Plan
| |
− | |-
| |
− | | || width="300px"|'''Note:''' Rustication shall be used on grade separations only. Terminate rustication 4 ft. 0 in. from end of wing.
| |
− | |}
| |
− | | |
− | | |
− | | |
− | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
| |
− | | |
− | |[[Image:751.12 joint and rustication details part section showing rustication details.gif]]
| |
− | |align="left"|'''Note:''' Rustication to be used on<br/>highway grade separation only.<br/>End rustication 4'-0" from end<br/>of wing.
| |
− | |-
| |
− | !Part Section Showing Rustication Details
| |
− | |
| |
− | |}
| |
| | | |
| === 751.12.2.8 Plastic Waterstop === | | === 751.12.2.8 Plastic Waterstop === |
Line 611: |
Line 190: |
| Use a plastic waterstop on lower safety barrier curb joint only, for structures with superelevation on grade separations. | | Use a plastic waterstop on lower safety barrier curb joint only, for structures with superelevation on grade separations. |
| | | |
− | | + | The detail for plastic waterstop is included on the [http://www.modot.org/business/standard_drawings2/Barrier_curbs_new_title_block.htm barrier curb standard drawings]. The detail shall be removed if not required. |
− | <center>[[Image:751.12 plastic waterstop on bridge filled joint detail.gif]]</center>
| |
− | <center>* Rustication to be used on highway grade separations only.</center>
| |
− | <center>'''Filled Joint Detail'''</center>
| |
| | | |
| === 751.12.2.9 Details of Mounting Light Poles on Safety Barrier Curbs === | | === 751.12.2.9 Details of Mounting Light Poles on Safety Barrier Curbs === |
| | | |
− | {|border="0" cellpadding="5" cellspacing="1" align="center" style="text-align:center"
| + | [[image:751.12.2.9 part.jpg|center|750px]] |
| + | [[image:751.12.2.9 section.jpg|center|750px]] |
| | | |
− | |[[Image:751.12 details of mounting light poles-part plan1.gif|300px]]
| + | Anchor bolts and nuts shall be in accordance with ASTM A449. Anchor bolts, nuts and washers shall be fully galvanized. |
− | |colspan="2"|[[Image:751.12 details of mounting light poles-part plan2.gif|325px]]
| |
− | |-
| |
− | !Part Plan
| |
− | !colspan="2"|Part Plan
| |
− | |-
| |
− | |[[Image:751.12 details of mounting light poles-section a-a.gif|330px]]
| |
− | |colspan="2"|[[Image:751.12 details of mounting light poles-section b-b 2010.gif|430px]]
| |
− | |-
| |
− | !Section A-A
| |
− | !colspan="2"|Section B-B
| |
− | |-
| |
− | |[[Image:751.12 details of mounting light poles bar shape 30.gif]]
| |
− | |[[Image:751.12 details of mounting light poles bar shape 13.gif]]
| |
− | |[[Image:751.12 details of mounting light poles bar shape 10.gif]]
| |
− | |-
| |
− | |colspan="3" align="left"|Anchor bolts and nuts shall be in accordance with ASTM F1554 Grade 55. Anchor bolts, nuts and washers shall be fully galvanized.
| |
− | |-
| |
− | |colspan="3" align="left"|'''Note to Detailer:''' Extend slab transverse steel to edge of slab in blister region.
| |
− | |-
| |
− | |colspan="3" align="left"|'''Note:''' Conduit not shown for clarity.
| |
− | |}
| |
| | | |
− | === 751.12.2.10 Superelevation Details ===
| + | '''Note to Detailer:''' Extend slab transverse steel to edge of slab in blister region often shown with an additional detail with the slab details. |
| | | |
− | <center>[[Image:751.12 superelevation details-section thru superelevated slab.gif]]</center>
| + | '''Note:''' Conduit not shown for clarity. |
− | <center>'''Section Thru Superelevated Slab'''</center>
| |
| | | |
| | | |
− | <center>[[Image:751.12 superelevation details-section thru superelevated approach slab at integral end bent.gif]]</center>
| + | === 751.12.2.10 Superelevation Details === |
− | <center>'''Section Thru Superelevated Approach Slab at Integral End Bent'''</center>
| |
| | | |
− | | + | [[Image:751.12.2.10 1.jpg|center|700px]] |
− | <center>[[Image:751.12 superelevation details-section thru superelevated approach slab at non-integral end bent.gif]]</center>
| + | [[Image:751.12.2.10 2.jpg|center|700px]] |
− | <center>'''Section Thru Superelevated Approach Slab at Non-Integral End Bent'''</center>
| + | [[Image:751.12.2.10 3.jpg|center|700px]] |
| | | |
| {|align="center" | | {|align="center" |
| | | |
− | |"A"|| = 2'-8" + (Superelev. Slope x 16") | + | |"A"|| = 32'-8" + S.E. x 16" |
| |- | | |- |
− | |"B"|| = 2'-8" - (Superelev. Slope x 16") | + | |B|| = 32'-8" - S.E. x 16" |
| |- | | |- |
− | |"C"|| = 8 1/2" + (Superelev. Slope x 16") | + | |C|| = 8 1/2" + S.E. x 16" |
| |- | | |- |
− | |"D"|| = 8 1/2" - (Superelev. Slope x 16") | + | |D|| = 8 1/2" - S.E. x 16" |
| |} | | |} |
− |
| |
− |
| |
| | | |
| == 751.12.3 Medians == | | == 751.12.3 Medians == |
751.12.1 Standard Safety Barrier Bridge Curbs
751.12.1.1 Standard Safety Barrier Curbs used in Missouri
|
Type A Test Level TL-4
|
Type B Test Level TL-4
|
NJ Shape
|
|
|
Type C Test Level TL-5
|
Type D Test Level TL-5
|
Note:
|
For Type F (Temporary Barrier Curb), refer to Missouri Standard Plans 617.20.
|
|
For Thrie Beam Rails, see Widening & Repair information.
|
|
See Structural Project Manager before using Type C or D barriers.
|
751.12.2 Safety Barrier Bridge Curbs (NJ Shape)
751.12.2.1 General Design
New safety barrier curbs "shall be shown to be structurally and geometrically crashworthy". Therefore, the shape of the safety barrier curb is selected based on crash-tested, or equivalent crash-tested geometry.
The safety barrier curb used on new bridges shall be the 16” New Jersey (MO) safety shape barrier curb which has been crash-tested and FHWA approved as meeting test level TL-4.
Test level TL-4 shall be used for safety barrier curb design. TL-4 is defined by AASHTO as being “generally acceptable for the majority of applications on high-speed highways, freeways, expressways, and interstate highways with a mixture of trucks and heavy vehicles”.
All exposed edges shall have either a 1/2-inch radius or a 3/8-inch bevel, unless otherwise noted.
The values shown above are only applicable for the standard normal crown of two percent. See EPG 751.12.2.10 Superelevation Details for adjustment of values for different cross slopes.
Material Properties
Concrete
|
|
Unit weight of reinforced concrete,
|
= 150
|
for modulus of elasticity,
|
= 145
|
Safety Barrier Curbs
|
|
Safety Barrier Curbs shall consist of:
|
|
Class B-1 Concrete
|
= 4.0 ksi
|
|
= 8
|
Median Barrier Curbs
|
|
Median Barrier Curbs shall consist of:
|
|
Class B-1 Concrete
|
= 4.0 ksi
|
|
= 8
|
Reinforcing steel
|
|
Minimum yield strength,
|
= 60.0 ksi
|
Steel modulus of elasticity
|
= 29000 ksi
|
751.12.2.2 Standard Reinforcement Details
The single R bar adds to the rigidity of the reinforcement during construction and it is believed to help prevent cracking. The single bar also appears to assist maintaining uniform
reinforcement cover.
Use same grade reinforcing steel in barrier curb as in slab.
Splice length for #5 bars in barrier curb shall be 37 inches.
All bars are epoxy coated. All bent bars are formed using stirrup bends except for the R1, K4 and K11 bars.
(No Wearing Surface)
Dimensions shown are also typical for structures with latex or low slump concrete (except as indicated).
(1¾” Wearing Surface)
(2¼” Wearing Surface)
751.12.2.3 End Bent Reinforcement
See barrier curb standard drawings for the placement of the following reinforcement.
All bars are epoxy coated. All bent bars are formed using stirrup bends except for the K4 and K11 bars.
Integral End Bents and Semi-Deep Abutments
* On skewed integral end bents, if the end K3 bars do not meet the minimum 1 1/2" clearance from the front face of the diaphragm, a K12 bar shall be substituted.
Non-Integral End Bents
751.12.2.4 Slip-Form Reinforcement Details
Optional slip-form safety barrier curb details shall be placed on all jobs (except prestressed double-tee structures) where applicable.
Add #5 cross bracing C bars for slip-form option.
In each span, the length of the C bars is based on the shortest distance between the joints for that span.
The length of the C bars above the wings (above the approach slab for median barriers) shall provide 1 1/2ʺ clearance to the joint at the end bent and 1 1/2ʺ clearance to the start of the transition for the guard rail attachment (to the end of the barrier for median barriers). A series of cross bracing C bars shall be used to limit the length of the C bars to 12 feet.
List C bars in the Bill of Reinforcing Steel and note that bars are for the slip-form option only.
See barrier curb standard drawings for the required details.
751.12.2.5 SBC for Wing with Detached Wing Wall
If the detached wing wall has more than one section, see the Structural Project Manager for possible additional joints in the safety barrier curb (between sections).
The following details are for illustration purpose only:
751.12.2.6 Guardrail Attachment Detail
See barrier curb standard drawings for the required details.
751.12.2.7 Joint Details
Curb Expansion Joints. Openings required for expansion shall be provided in the barrier curb in conjunction with deck joints. For details of expansion joints in barrier curb see expansion device details.
Curb Joints. 1/4 in. joints are located in the barrier curb at locations of negative moments to prevent cracking in the barrier curb. These joints are required when decks are continuous over intermediate bents for both continuous and simple span structures. These joints are also required at the front face of integral end bents. For placement of curb joints at integral end bents see integral end bent details. The following details provide guidance on locating curb joints near intermediate bents.
The details for curb joints are included on the barrier curb standard drawings.
751.12.2.8 Plastic Waterstop
To eliminate water seepage problems, use a plastic waterstop, as specified, and in accordance with details shown below.
Use a plastic waterstop at all safety barrier curb joints on grade separations, except over railroads and county roads.
Use a plastic waterstop on lower safety barrier curb joint only, for structures with superelevation on grade separations.
The detail for plastic waterstop is included on the barrier curb standard drawings. The detail shall be removed if not required.
751.12.2.9 Details of Mounting Light Poles on Safety Barrier Curbs
Anchor bolts and nuts shall be in accordance with ASTM A449. Anchor bolts, nuts and washers shall be fully galvanized.
Note to Detailer: Extend slab transverse steel to edge of slab in blister region often shown with an additional detail with the slab details.
Note: Conduit not shown for clarity.
751.12.2.10 Superelevation Details
"A" |
= 32'-8" + S.E. x 16"
|
B |
= 32'-8" - S.E. x 16"
|
C |
= 8 1/2" + S.E. x 16"
|
D |
= 8 1/2" - S.E. x 16"
|
751.12.3 Medians
751.12.3.1 Double Faced Median Barrier Curb (NJ Shape)
Note: |
Use same grade reinforcing steel in barrier curb as in slab.
|
|
Splice length for #5-R bars in barrier curb = 37".
|
|
Do not use this barrier curb over precast prestressed panels.
|
Note to detailer: |
Provide slip-form option for double faced median safety barrier curb. For slip-form option additional #5 cross bracing bars shall be placed on both sides of all joints and R2 bars shall be one bar.
|
|
|
R2 Bar Shape 15
|
R4 Bar Shape 27
|
|
Section Thru Double Faced Median Barrier Curb
|
|
Twin Bridge Median Barrier Curb Details
|
|
Section Thru Median with Open Joint
|
751.12.3.2 Concrete Median Curbs
|
Open Joint (Twin Bridges Typ.)
|
|
Barrier Class (No Joint)
|
|
Mountable Class
|
Note: All reinforcement shown shall be epoxy coated.
|
Details shown are very general. Consult Design Layout for specific details for each individual structure.
|
Concrete Median Curbs (Permissable Alternates)
Bent Bar:
|
|
|
Open Joint (Twin Bridges Typ.)
|
Barrier Class (No Joint)
|
|
|
Detail "A"
|
Detail "B"
|
|
Add note to plans:
|
No additional payment will be allowed for the usage of either alternate anchoring systems.
|
Resin Anchor:
|
|
Note: All reinforcement shown shall be epoxy coated.
|
751.12.4 Chain Link Fence
|
Superstructure Near Steps
|
|
|
Superstructure at or Near End Panel
|
|
|
Design Crieria: Fence fabric weight = 10#/lin. ft. Eff. wind area = 0.11 area/sq.ft.
|
Detail "A"
|
|
(112") Curved top Pedestrian Fence (Structures)
(Optional fence detail when requested by district or railroad personnel)
|
|
Section A-A
|
|
|
Curved Top Pedestrian Chain Link Fence (Galv. Steel) on Sidewalk
|
NOTE: 8'-0" Max. post spacing for superstructure.
(*) Locate at about 30'-0" centers with at least one splice gap between pull posts.
The maximum spacing allowed between pull posts and end posts is 100 feet. Post brace and 1/2"Ø truss rod are required for panels adjacent to pull posts and end posts only. Connect the lower end of the 1/2"Ø truss rod to the bottom of the pull posts and end posts to which the stretcher bar is attached.
|
|
|
Details at Expansion Device Gap
|
(**) May conflict with any proposed expansion device sidewalk, consult Structural Project Manager.
|
|
|
Typical Section Near Splice Gap
|
Note: 8'-0" max. post spacing for superstructure.
(*) Locate at about 30'-0" centers with at least one splice gap between pull possts and end posts.
|
751.12.5 Two Tube Rail (Top Mounted) TL-4 (NCHRP 350)
Guidance
- Meets TL-4 (NCHRP 350)
- Typically used on spread box beam bridges.
- May be used on adjacent box beam bridges where reinforcement is embedded in the beam.
- Use only in certain applications because of cost.
- Acceptable for use when roadway width or site distance is a concern.
- Curb is intrinsic to TL rating and shall be used. Curb shall be used to prevent drainage over deck.